FS4000 8 Zones Conventional Fire Alarm Panel

FS4000 8 Zones Conventional Fire Alarm Panel
FS4000 8 Zones Conventional Fire Alarm Panel
Be PVM
82.20€
Su PVM: 99.46€
  • Stock: In Stock
  • Model: FS4000 - 8

8 zones fire control panel FS4000 is designed to operate with conventional automatic fire detectors and manual call points. The panel has outputs provided for external executive devices.

Technical specification:

Fire alarm lines:
   - Maximum number of fire detectors in a line - 32
   - Connecting line - two wire
   - Maximum resistance of a line - 100 ohm

Current thresholds for:
   - Fault condition - 0-6mA
   - Duty mode - 6-18 mA
   - Fire condition - 18-80mA
   - Short circuit - >80mA
Controllable outputs for fire condition:
   - Number - 2 pcs;
   - Type - potential, relay with independent control
   - Electrical characteristics - (19-28)V DC/1 A
Relay outputs for fire condition:
   - Number - 2 pcs
   - Type - potential-free, switching with independent control
   - Electrical characteristics - 3А/125V AC, 3A/30V DC
Relay output for fault condition:
   - Number - 1 pcs
   - Type - potential-free, switching with independent control
   - Electrical characteristics - 3А/125V AC, 3A/30V DC

Performance:
-    Control over fire alarm lines and controllable outputs for fault conditions (short circuit and interruption) and automatic reset.
-    Detection of removed fire detector and automatic reset.
-    Identification of manual call points.
-    LED indication for alarm state and emergency.
-    Delay of outputs for fire condition with time period of 1, 2, 3, 4, 5, 6  or 7 minutes after fire condition is registered.
-    Option for ''LOGICAL AND '' realization of two fire alarm lines.
-    Duty Mode condition with direct activation of Fire Condition 2nd Stage '' for two fire alarm lines.
-    Status Indication of the device for data transmission RS485.
-    Option for switching  on/off  interface RS485 communication.
-    Built-in sounder for fire condition – one tonal, continuous, can be switched off.
-    Built-in sounder for fault condition – one tonal, discontinuous, can be switched off.
-    Test mode for fire alarm lines.
-    Disabling fire alarm lines.
-    Disabling outputs for fire condition.
-    Expanding the options by means of extra relay outputs for fire condition for each line and built-in RS485 for operation in a local network.

Indications of registered events:
   - Light indication - LED
   - Sound - Built-in sounder

Power supply
   - Mains:
          Voltage - (187-252)V AC
          Frequency - 50/60 Hz
   - Backup batteries:
          Battery type - lead, gel electrolyte
          Number of batteries - 2 pcs
          Nominal voltage of the backup battery - 12V
          Nominal capacity C20 - (7) Ah
          Charge voltage - 28V DC
          Operation in Duty mode upon interruption in main power supply:
          90 h (24V / 7Ah),

   Power supply to external devices:
   - Voltage - (19-28)V DC
   - Maximum current value (including current of contr.outputs) - 1,2A

Dimension - 304х222х94mm
Weight (backup batteries not included) - 1,5 kg